>Product>Thermo-hydrostat>UP TYPE
Up type size
MODEL DCA- 3AU DCA- 5AU DCA- 7.5AU DCA- 10AU DCA- 15AU DCA- 20AU
External size L(length) 730 880 1180 1480 1850 2050
W(width) 650 750 750 750 850 890
H(height) 1950 1950 1950 1950 2200 2200

UP TYPE spec

MODEL

DCA-3AU

DCA-5AU

DCA-7.5AU

DCA-10AU

DCA-15AU

DCA-20AU

Power

220/380V 3Ph 60Hz

Cooling capacity(Kcal/hr)

8,100

13,500

20,250

27,000

40,500

54,000

Heating capacity(Kcal/hr)

6,880

8,600

12,040

17,200

20,640

24,080

Blower

MODEL
(Sirocco Fan)

1 1/2DS×1EA

1 3/4DS×1EA

2DS×1EA

1 3/4DS×2EA 

2DS×2EA

2 1/2DS×2EA

Motor power
(Kw x P x EA)

0.3×8P×1

1.1×6P×1

2.0×6P×1

1.1×6P×2

2.0×6P×2

3.0×6P×2

Static pressure in unit
(mm/Aq)

15~20

Air volume(CMM)

36

60

90

120

180

240

Heater

Type

AERO FINNED TUBE

Capacity
(Kw*Step)

8(4×2)

10(2.5×4)

14(3.5×4)

20(5×4)

24(6×4)

28(7×4)

Humidifier

Type

Electrode type

Humidifying amount
(Kg/hr)

2.4

3.6

6

7.2

8.4

9.6

Control method

MICOM CONTROLLER

Control device

Overcurrent relay, electronic switch, auxiliary generator

Interior part

FILTER DRYER, GAUGE(high/low voltage), solenoid valve, expansion valve, SIGHT GLASS

Protective device

DUAL PRESS S/W, HIGH PRESS S/W, AIR FLOW S/W

Outdoor machine

DCACU-3

DCACU-5

DCACU-7.5

DCACU-5*2set

DCACU-7.5*2set

DCACU-10*2set

 
※ The product may change depending on technical development. For the product with special spec, which does not belong to the products above, we manufacture it after receiving an order.